STD-UI1 — single-phase meter
Member of the rbAmp STD family; everything on the family page applies.
What it is
A single-phase precision energy meter module: one voltage and one current input with synchronous
sampling, the full STD feature set, and a choice of I²C or Modbus RTU. Variant code 0x11.
It works as a sub-meter / smart-meter front end for a master (ESP32, Arduino, Raspberry Pi, PLC), or directly on a Modbus RTU network (through an external RS-485 transceiver) as a meter, including a float32 register profile of 13 values for inverters and monitoring systems (Modbus transport).
Key properties
| Inputs | 1 voltage, 1 current (factory-matched sensor, labelled for the channel; 60 A or 100 A in the kit) |
| Quantities | U, I, P (signed), Q, S, PF (signed), frequency; import/export energy, active and reactive |
| Energy counters | Wh, mWh, µWh (active) and varh, µvarh (reactive); kept when the power is off |
| Interfaces | I²C (0x50 by default) or Modbus RTU (unit 1, 9600 8N1 by default), chosen by the interface mode switch |
| Snapshot cadence | a complete snapshot about ten times a second; data-ready output |
| Period snapshots | eight independent banks |
| Update | over the working bus, with automatic rollback |
Measured characteristics
Measured on one production module per kit (60 A and 100 A), each channel individually calibrated together with its sensor, against a reference meter on a resistive load. Current is given as the primary current with one pass of the wire through the sensor; on STD-U3I3 the figures cover all three channels.
| Parameter | 60 A kit | 100 A kit |
|---|---|---|
| Current error | ±0.2 % in range 0.005 A – 75 A | ±0.2 % in range 0.005 A – 100 A |
| Upper end of the range | 75 A | 129 A |
| Voltage error | ±0.2 % | ±0.2 % |
| Power factor, resistive load | 0.999–1.000 | 0.999–1.000 |
| Reads from | 4.8 mA | 4.8 mA |
| Noise with no current | 0.2 mA | 0.35 mA |
Typical uses
- The main meter of a single-phase home, apartment or workshop.
- Sub-metering of a circuit, a heater, an EV charger or a heat pump.
- Solar self-consumption: separate import and export energy, the float32 profile points for a Modbus master.
- A measuring node in a Home Assistant / ESPHome installation.
Where to go next