Modbus RTU transport

On the Modbus setting of the interface mode switch the module is a Modbus RTU slave on its UART lines (an external transceiver adapts them to RS-485). The Modbus layer is a translation onto the same register file as I²C: same quantities, same commands, one command queue; only the wire format differs.


Serial

  • Framing: standard RTU [addr][function][data][CRC16], CRC16 poly 0xA001 (reflected), LSB first. A frame with a bad CRC gets no answer (standard RTU behaviour).
  • Unit id: 1..247, default 1 (CFG_MODBUS_ADDR). 0 = broadcast (whitelisted writes only, see below). Ids 248..255 are rejected on configuration.
  • Baud: default 9600. Codes in CFG_MB_BAUD: 0=2400 · 1=4800 · 2=9600 · 3=19200 · 4=38400 · 5=57600 · 6=115200 · 7=230400 · 8=460800 · 9=921600 · 10=1 000 000. The module accepts codes 0–10; the line speed over RS-485 is set by the external transceiver. If the stored code is ever invalid, the module boots at 9600.
  • Frame format: CFG_MB_FRAME 0=8N1 · 1=8E1 · 2=8O1 · 3=8N2.
  • Response hold-off: CFG_TX_DELAY 0..100 ms — for auto-direction RS-485 adapters that need time to release the line.
  • Serial settings are validated on write (exception 03). A write only stages the value in RAM — to make it effective: save (COMMAND 0x04), then restart (COMMAND 0x02, UNLOCK-gated); the module boots with the saved values. Step-by-step: Sequences D4.
  • Reply latency: the requested range is copied atomically out of the published image, so even a 125-register read is internally coherent; the device answers in < 20 ms at any baud (suited to inverter polling at 3–5 Hz).
  • Replies to restart-causing commands (RESET, firmware ACTIVATE, address change by UID) may be truncated or absent — the device may restart before the reply completes, and a configured TX delay can suppress it entirely. Confirm by re-polling after the restart, not by the reply.

Function codes

FC03 read holding · FC04 read input · FC06 write single · FC16 write multiple. Any other function code → exception 01.

Limits: FC03/FC04 quantity 1..125, FC16 1..123 — outside → exception 03. FC16 is all-or-nothing: the whole frame is validated first; one bad register → nothing applied. COMMAND (holding 0x8113) is write-only — reading it → exception 02.


Register spaces

Modbus addresses are their own namespace — independent of I²C addresses. Layout:

Space Range Content
Input 0x0000–0x03FF Float32 profile (13 live points, below)
Input 0x6000–0x6FFF native integer-scale profile (discovery, channels, energy, totals)
Holding 0x8000–0x83FF native config · time/commands · firmware update
Holding 0x8400–0x847F security window (device certificate / attestation; byte stream)
Holding 0xA000–0xAFFF read-only mirror of native input (= input address + 0x4000) for FC03-only masters
— everything else unmapped → exception 02

The per-block native and holding addresses are listed with the I²C map in the register map.

Native profile (input 0x6000+)

Fixed-scale integers, same units as I²C. Word order ABCD (high word first) by default; CFG_WORD_ORDER = 1 swaps to low-word-first for all multi-register numbers in the native input profile (i64 = all four words reversed), and the absent-channel sentinels swap the same way. The holding windows (0x81xx/0x83xx) are always high-word-first, regardless of CFG_WORD_ORDER. i32 = 2 registers, i64 = 4 registers. Totals P/Q/S are published as i64 over Modbus (sign-extended from the device values).

Float32 profile (input 0x0000)

Modbus RTU with a float32 register profile of 13 values. The register addresses and the ABCD word order follow the publicly documented SDM register map. We have not tested the module against any SDM device, or against third-party SDM software, an inverter, a PLC or a SCADA system.

IEEE-754 float32, ABCD always, physical units (V/A/W/kWh), export as positive magnitude. Live points (13):

Input addr Point
0x0000 / 0x0002 / 0x0004 voltage L1 / L2 / L3, V
0x0006 / 0x0008 / 0x000A current L1 / L2 / L3, A
0x000C / 0x000E / 0x0010 active power L1 / L2 / L3, W
0x0034 total active power, W
0x0046 frequency, Hz
0x0048 / 0x004A import / export energy, kWh

Every other address in 0x0000–0x03FF reads 0; an inverter or SCADA that needs registers outside the list above does not get them from this profile. Phases the module does not have read 0.0 (STD-UI1 publishes its channel as L1; its L1 addresses carry voltage, current, power, frequency, import and export energy). S, Q, PF and total energy points read 0. Single-phase members publish their channel as L1. This profile has no configuration aliases — configuration is done through the native holding registers.

Virtual unit ids

With CFG_VIRTUAL_IDS = 1 (saved + restart; takes effect at boot) a module with more than one current channel also answers on unit ids base+1 … base+N_CURRENT (clamped at 247): each id is a read-only single-channel float32 view of one current channel — its voltage, current, power, total power = that channel's power, frequency; energy points read 0. Any write to a virtual id → exception 02. Pick the base unit id so the derived ids do not collide with other meters on the bus.

(The METER_GROUP configuration table in the map is reserved — group composition is not configurable.)


Broadcast (unit id 0)

Only these writes are accepted on broadcast; everything else is silently refused (no exception response on broadcast, per the Modbus standard):

  • time set — two frames: FC16 to 0x8100–0x8101 (epoch, high word first), then FC06 COMMAND 0x8113 = 0x0006 — bus-wide clock sync;
  • LATCH_BANK / PERIOD_ARM 0x8110–11 and COMMAND 0x03 — synchronized snapshot across modules (capability bit 8);
  • address-by-UID staging 0x8118–0x811E + COMMAND 0x16 — commissioning on a shared bus.

A broadcast FC16 must stay within the whitelisted registers — a frame that touches anything else is refused as a whole.


UNLOCK (gated commands)

Commands that change device state must be preceded by writing the unlock key 0xA5C3 to holding 0x8112:

  • The key is valid for 10 s and is consumed by one gated command.
  • Writing a wrong value clears an active unlock.
  • A gated command without a valid unlock → exception 03.
  • Reading 0x8112 returns the unlock flag (0/1) as last set — treat it as informational only.
  • Unlock and command may go in one FC16 frame at 0x8112–0x8113 (key first, opcode second).

Gated set: 0x01 SAVE_CAL · 0x02 RESET · 0x07 ENERGY_RESET (where implemented) · 0x10/0x12/0x13/0x14 (firmware update) · 0x15 (service). Not gated: 0x04 SAVE_CONFIG · 0x06 SET_TIME · 0x08–0x0F · 0x11 page write · 0x16 address by UID. On modules that do not implement an opcode the refusal is exception 03 before the gate is even checked. The life-time energy commands use a different, single-shot key mechanism (LT_KEY), not UNLOCK — see Commands.


Behaviour rules (family contract)

  • COMMAND, LATCH_BANK, PERIOD_ARM values > 0xFF → exception 03 (no silent low-byte truncation).
  • A COMMAND write while a command is still executing → exception 06 (device busy).
  • Byte-pair windows (security 0x8400+, firmware payload 0x8380+, history record 0x8180+): register k carries bytes 2k (high) and 2k+1 (low). Writes that touch read-only bytes → exception 02. The security window is a little-endian byte stream — numeric fields inside it decode LE from the bytes, not as big-endian registers.
  • One table of legal configuration values serves both transports: an illegal value over Modbus → exception 03; the same value over I²C is refused at SAVE_CONFIG with ERROR 0xFD — in both cases nothing is persisted.
  • Fields the build does not offer (absent channels; THD and displacement quantities with CAPABILITIES bit 2 = 0) read the sentinel in the native profile (0xFFFF / 0x8000…); in the float32 profile they read 0.

Exceptions

Code Meaning
01 illegal function (anything but FC03/04/06/16)
02 address outside the map · write to an input register, read-only holding or virtual unit id · read of a write-only register
03 illegal value (bad unit id / baud code / config value · invalid command opcode · oversized COMMAND/LATCH value · quantity out of range · gated command without unlock)
04 internal device failure
06 device busy (command or firmware operation in progress)

The last exception is kept for diagnostics in LAST_EXCEPTION (FC<<24 | code<<16 | address), readable on both transports: I²C 0x0158, Modbus holding 0x830A–0B.