Passa al contenuto

How accurate is rbAmp?

30 luglio 2026 di
How accurate is rbAmp?
Administrator

It depends on the current sensor, so the figure has two parts: the module's class with the SCT-013 rating you use, and the clamp's own tolerance added on top. Both are given per rating — together with the floor below which a current is seen but not measured to that class — in the SCT-013 accuracy table. In the working range (5–100 % of the rating) the class is ≤ 0.5 % for most ratings.

It measures true active power — the mean of instantaneous voltage × current over the line cycle, with per-channel phase compensation — not current × assumed-voltage apparent power.

For a whole-panel figure summed across several modules, the channel errors add up rather than average out, so we never quote a summed total as tighter than a single channel. More on the physics: how CT energy measurement really works.

Documentation & source code
📖 rbAmp documentation overview · 💻 rb-amp/rbamp-docs on GitHub
Is the rbAmp module isolated from mains?